 SPRINKLER
SYSTEMS
MONITORING
ZONECHECK Flow Switch Tester
Manifold Models
UL/FM Models with 110 V Pump ZC20 ZC25 ZC30 ZC40 ULC Models with 110 V Pump ZC20A ZC25A ZC30A ZC40A ZONECHECK Manifold Model
Retrofit Models
UL/FM Models with 110V Pump ZCR20 ZCR25 ZCR30 ZCR40 ZCR60 ZCR80 ULC Models with 110V Pump ZCR20A ZCR25A ZCR30A ZCR40A ZCR60A ZCR80A International Models with 220V Pump ZCR20E ZCR25E ZCR30E ZCR40E ZCR60E ZCR80E
Replacement Parts
ZCK-1 ZONECHECK 110V Keyswitch ZCK-1E ZONECHECK 220V Keyswitch ZCK-1EG ZONECHECK 220V Keyswitch (German) ZCP-110 ZONECHECK 110V Pump ZCP-220 ZONECHECK 220V Pump ZCRK ZONECHECK Replacement Kit
Product Overview Simplifies compliance to NFPA 25 for quarterly flow switch testing Does not require opening the inspector's test connection Saves as much as 400 gallons of water per flow switch per year Does not activate the building's fire pump Testing initiated by a key switch Key switches may be interconnected to control all ZONECHECKs from one master switch Significantly reduces testing time Includes a System Sensor flow switch with each model Offered in manifold and retrofit configurations System Sensor's ZONECHECK flow switch tester is an automatic method for performing quarterly flow switch tests per NFPA 25. Code Compliance. Quarterly flow switch tests are mandated by NFPA 25. ZONECHECK simplifies testing by re-circulating the water within the pipe around the flow switch, to simulate the flow of one sprinkler head in operation. This simulation is achieved without having to open the inspector's test connection. Environmental Savings. ZONECHECK re-circulates the water within the pipe, so no
water is expelled from the system. Over the course of one year, ZONECHECK can save as much as 400 gallons of water per flow switch, per year.
Ensured Life Safety. Since ZONECHECK does not require opening the inspector's test connection, a building's fire pump is not activated, to avoid unnecessary fire department dispatches. This also reduces the likelihood of the fire pump being turned off manually during flow switch testing, thereby ensuring the sprinkler system's integrity. Time Savings. ZONECHECK's pump is activated by the turn of a key switch. The key switch may be wired to initiate one pump locally, or can be interconnected. When interconnected, any key switch may activate all ZONECHECK pumps, to significantly reduce testing time. Applications Flexibility. All ZONECHECKs are equipped with a System Sensor flow
switch. Models include manifold and retrofit configurations with either 110V or 220V pumps, and UL, ULC, or International style flow switches.
Standard Specifications Working Pressure Rating 175 PSI Operating Temperature Range 32F - 120F (0C - 49C) Compatible Pipe (Manifold Models) Schedule 10, 2 - 4 diameter Compatible Pipe (Retrofit Models) Schedule 10 and 40, 2 - 8 diameter (50 mm through 200 mm) Ser vice Use Inspection, Testing and Maintenance of Water-Based Fire Protection Systems: NFPA25 National Fire Alarm Code: NFPA 72 Manifold Assembly Length (Manifold Models) 25.6 (65 cm) Component Connections (included) (Manifold Models) 2 - 1 NPT/25mm British Standard Thread elbows Component Connections (included) (Retrofit Models) 2 - 1 NPT/25mm British Standard Thread elbows 2 - 25mm British Standard Thread elbows Valves (included) Red: Standard valve Green: Contains check valve Warranty 3 years Approximate Weight Style ZCR20 ZCR25 ZCR30 ZCR40 ZCR60 ZCR80 ZC20 ZC25 ZC30 ZC40 Weight 31 lbs. (14.1 kg) 31.5 lbs. (14.3 kg) 32 lbs. (14.5 kg) 33 lbs. (14.9 kg) 34 lbs. (15.4 kg) 35 lbs. (15.9 kg) 37 lbs. (16.8 kg) 39 lbs. (17.7 kg) 41 lbs. (18.6 kg) 45 lbs. (28.8 kg)
Electrical Specifications Pump Operating Voltages UL, ULC, FM models: 1.63A @ 110V, 60Hz International models : 0.88A @ 220V, 50Hz Key Switch Operating Voltage ZCK-1: 110VAC ZCK-1E, ZCK-1EG: 220VAC Key Switch Mounting Options Includes back box for sur face or flush mounting. For pre-wiring, use a 41116 x 41116 back box. Flow Switch Included with ZONECHECK UL/FM Models with 110V Pump Retrofit Model ZCR20 ZCR25 ZCR30 ZCR40 ZCR60 ZCR80 Manifold Model ZC20 ZC25 ZC30 ZC40 Flow Switch Model Included WFD20 WFD25 WFD30-2 WFD40 WFD60 WFD80 Key Switch Operation Modes Self-test: Wired locally Group test: Interconnected Key Switch LED Operation Ready state: No LED Test initiation: Green LED Flow switch activation: Red LED for ZCK-1 Flow switch activation: Green LED for ZCK1E + ZCK1EG
ULC Models with 110 V Pump Retrofit Model ZCR20A ZCR25A ZCR30A ZCR40A ZCR60A ZCR80A Manifold Model ZC20A ZC25A ZC30A ZC40A Flow Switch Model Included WFD20A WFD25A WFD30-2A WFD40A WFD60A WFD80A
International Models with 220V Pump Retrofit Model ZCR20E ZCR25E ZCR30E ZCR40E ZCR60E ZCR80E Flow Switch Model Included WFD20E WFD25E WFD30E WFD40E WFD60E WFD80E
For flow switch specifications, refer to the appropriate flow switch instructions manuals.
ZONECHECK Installation For flow switch specifications, refer to the appropriate flow switch instructions manuals. WATERFLOW DETECTOR ZONECHECK PUMP RED VALVE GREEN VALVE RED VALVE
WATERFLOW DETECTOR
ZONECHECK PUMP
CORRECT
Correct Horizontal Installation Pump stripes (horizontal)
GREEN VALVE
Correct Vertical Installation
INCORRECT
Pump stripes (vertical) ZONECHECK PUMP
ZONECHECK PUMP Incorrect Horizontal Installation Electrical Wiring Diagrams
FOR INTERCONNECTING MULTIPLE ZONECHECK UNITS
TO EARTH GND. OR ATTACH TO JUNCTION BOX GND AC AC PUMP PUMP AC POWER
Incorrect Horizontal Installation
AC GROUND
WIRING DIAGRAM FOR STAND ALONE APPLICATION
TO EARTH GND. OR ATTACH TO JUNCTION BOX GND AC AC PUMP PUMP PUMP AC POWER WATERFLOW DETECTOR
AC GROUND
} }
WF INPUT INTER-CONNECT
} }
WF INPUT INTER-CONNECT TO EARTH GND. OR ATTACH TO JUNCTION BOX GND AC AC PUMP PUMP PUMP AC POWER
WATERFLOW DETECTOR
AC GROUND
NOTE: WF INPUT NOT REQUIRED FOR KEYSWITCH OPERATION IF WATERFLOW DETECTOR IS CONNECTED TO PANEL OR OTHER MONITORING DEVICE. AC POWER AND PUMP WIRING MUST CONFORM TO NEC OR YOUR LOCAL CODES.
} }
WF INPUT INTER-CONNECT
WATERFLOW DETECTOR
PUMP TO NEXT ZONECHECK SWITCH FOR INTERCONNECT
Engineering Specifications General/Retrofit Model Specifications Model shall be a ZONECHECK Flow Switch Tester model ___________________ as manufactured by System Sensor. Flow Switch Tester shall be installed on a sprinkler system riser as designated on the drawings and/or as specified herein. Flow Switch Tester assembly shall mount on any clear pipe span of the appropriate nominal size, either in a ver tical upflow or horizontal run, between 6 and 12 from the flow switch. Flow Switch Tester shall consist of a recirculating pump, operating at nominal 110V or 220V as appropriate, two (2) sets of valves and elbows to facilitate the circulation of the water, a System Sensor vane-type waterflow detector, and a key switch to activate the recirculating pump. When activated, the pump shall circulate the water within the sprinkler riser around the water flow detector vane to simulate the flow of one sprinkler head in operation. The activating key switch shall provide the means to be wired locally to one ZONECHECK Flow Switch Tester, or interconnected with other key switches for group activation. Flow Switch Tester shall be available for manifold and retrofit installation applications. ZONECHECK Flow Switch Tester retrofit models shall be listed by Under writers Laboratories, Inc. Manifold Model Specifications ZONECHECK Automatic Flow Switch Tester manifold models shall fur ther consist of a schedule 10 pipe assembly of the appropriate nominal size. Manifold assembly shall provide grooved ends for accepting the appropriate grooved connection fittings. Manifold assembly shall include no less than two drain por ts with the appropriate drain plugs. Manifold ZONECHECK models shall come with the pump, valves, elbows, pipe assembly, drain plugs, and System Sensor water flow detector pre-assembled. ZONECHECK Flow Switch Tester manifold models shall be listed by Under writers Laboratories, Inc.
Ordering Information Manifold Model Number ZC20 ZC25 ZC30 ZC40 ZC20A ZC25A ZC30A ZC40A Retrofit Model Number ZCR20 ZCR25 ZCR30 ZCR40 ZCR60 ZCR80 ZCR20A ZCR25A ZCR30A ZCR40A ZCR60A ZCR80A ZCR20E ZCR25E ZCR30E ZCR40E ZCR60E ZCR80E Pipe Size 2 2 1/2 3 4 2 2 1/2 3 4 Pipe Size 2 2 1/2 3 4 6 8 2 2 1/2 3 4 6 8 50 mm 65 mm 80 mm 100 mm 150 mm 200 mm Pump Voltage 110V 110V 110V 110V 110V 110V 110V 110V Pump Voltage 110V 110V 110V 110V 110V 110V 110V 110V 110V 110V 110V 110V 220V 220V 220V 220V 220V 220V Flow Switch WFD20 WFD25 WFD30-2 WFD40 WFD20A WFD25A WFD30-2A WFD40A Flow Switch WFD20 WFD25 WFD30-2 WFD40 WFD60 WFD80 WFD20A WFD25A WFD30-2A WFD40A WFD60A WFD80A WFD20E WFD25E WFD30E WFD40E WFD60E WFD80E
Replacement Model No. Description ZCK-1 ZCK-1E ZCK-1EG ZCP-110 ZCP-220 ZCRK 110V Keyswitch 220V Keyswitch 220V Keyswitch (German) 110V Pump 220V Pump ZONECHECK Replacement Kit
System Sensor Sales and Service
System Sensor Headquarters 3825 Ohio Avenue St. Charles, IL 60174 Ph: 800/SENSOR2 Fx: 630/377-6495 Documents-on-Demand 800/736-7672 x3 www.systemsensor.com System Sensor Canada Ph: 905.812.0767 Fx: 905.812.0771 System Sensor Europe Ph: 44.1403.276500 Fx: 44.1403.276501 System Sensor in China Ph: 86.29.524.6253 Fx: 86.29.524.6259 System Sensor in Singapore Ph: 65.6273.2230 Fx: 65.6273.2610 System Sensor - Far East Ph: 85.22.191.9003 Fx: 85.22.736.6580 System Sensor - Australia Ph: 613.54.281.142 Fx: 613.54.281.172 System Sensor - India Ph: 91.124.637.1770 x.2700 Fx: 91.124.637.3118
(c) 2003 System Sensor. The company reserves the right to change product specifications without notice.
A05-0272-003*02/03*#1070


▲Up To Search▲   

 
Price & Availability of ZONECHECK

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X